How Many Wires Fit in a Box?

Updated 2026-11-22

A 4 × 2-1/8 inch square box (30.3 in³) holds 15 #14, 13 #12 or 12 #10 conductors with nothing else inside. A device counts as two conductors and grounds and clamps one each, so with a receptacle, grounds and clamps it holds 9 #12 (NEC 314.16).

The calculator is set for an 18 in³ device box with one receptacle, grounds, internal clamps and 4 × 12 AWG, the most that fit. Change the box volume to match yours.

0#14
4#12
0#10
0#8
1
2
in³
Volume Required
18.00in³
Box is 18 in³ · 0.00 in³ free
Fits the box
Required
18.00
Box vol
18.00
Free
0.00
NEC 314.16
Report for your inspector

Maximum conductors per box, by size

Box (volume)#14 AWG · empty#12 AWG · empty#10 AWG · empty#14 AWG · with device#12 AWG · with device#10 AWG · with device
3 × 2 × 2-1/2 in device box (12.5 in³)655211
3 × 2 × 2-3/4 in device box (14.0 in³)765321
3 × 2 × 3-1/2 in device box (18.0 in³)987543
4 × 1-1/2 in octagon box (15.5 in³)766322
4 × 2-1/8 in octagon box (21.5 in³)1098654
4 × 1-1/2 in square box (21.0 in³)1098654
4 × 2-1/8 in square box (30.3 in³)1513121198
4-11/16 × 1-1/2 in square box (29.5 in³)1413111097
4-11/16 × 2-1/8 in square box (42.0 in³)211816171412
  • Computed with the Fieldwatt box fill engine from the nominal box volumes in NEC Table 314.16(A) and the per-conductor allowances in Table 314.16(B).
  • "Empty" means only current-carrying conductors of one size. "With device" also counts one device (2 allowances), all equipment grounds (1) and internal clamps (1), all at the same wire size.
  • Plastic boxes are not in the table. Use the volume marked inside the box with the calculator above.

NEC references

  • NEC 314.16(A) — box volume, and Table 314.16(A) nominal volumes for metal boxes
  • NEC 314.16(B) — what counts toward fill: conductors, devices, grounds, clamps
  • NEC Table 314.16(B) — volume allowance per conductor size

Frequently asked questions

How many 12 gauge wires can go in a box?

Divide the box volume by 2.25 cubic inches. An 18 in³ device box holds 8 conductors of 12 AWG with nothing else in it, or 4 with one receptacle, grounds and internal clamps.

How many 14 gauge wires fit in a 4 inch square box?

A 4 × 1-1/2 inch square box (21 in³) holds 10 #14 conductors, and the deeper 4 × 2-1/8 inch box (30.3 in³) holds 15. With a device, grounds and clamps inside, those drop to 6 and 11.

What counts toward box fill?

Each conductor that enters the box counts once at its size. Each device yoke counts as two of the largest conductor connected to it, all equipment grounds together count once, and internal clamps count once (NEC 314.16(B)). Pigtails that start and end inside the box do not count.

Do plastic boxes follow the same chart?

No. NEC Table 314.16(A) lists metal boxes only. Nonmetallic boxes are marked with their volume by the manufacturer, usually molded inside the box. Enter that number in the calculator above to get the count.

Take this calculator offline — free on Android

Get it on Google Play

Related calculators and charts