How Far Can You Run Wire?

Updated 2026-11-22

A 12 gauge copper circuit on a 20 A breaker at 120 V can run about 45 feet one way before voltage drop passes 3%. At 80% load (16 A) that stretches to 56 feet, and on 240 V it doubles to 91 feet. For a longer run, step up to 10 gauge.

The calculator is set for a 120 V, 20 A circuit on 12 AWG copper at 50 feet. Enter your own run length to see whether it stays under 3%.

V
A
ft
Voltage Drop
3.29%
3.95 V lost over 50 ft · 116.0 V at the load
Exceeds 3% limit
End voltage
116.0 V
Volts lost
3.95 V
Min size
#10 AWG
↑ Upsize to #10 AWG copper to pass. Per NEC 250.122(B), increase the EGC proportionally too.
  1. 1-phase multiplier 2
  2. K, copper ×12.9Ch.9 Tbl 8
  3. Load ×20 A
  4. One-way length ×50 ft
  5. #12 AWG circular mils ÷6,530Ch.9 Tbl 8
  6. Volts lost =3.95 V
  7. System voltage ÷120 V
  8. Recommended max Limits≤3%215.2(A)
  9. Voltage drop =3.29%

Numbers and NEC section numbers only. The AHJ and field conditions govern.

NEC 215.2(A) · Ch.9 Tbl 8
Report for your inspector

Longest one-way run (feet) at 3% drop, single-phase copper

Wire · breaker120 V · full load120 V · 80% load240 V · full load240 V · 80% load
#14 AWG · 15 A38477695
#12 AWG · 20 A455691113
#10 AWG · 30 A486096120
#8 AWG · 40 A5771115143
#6 AWG · 55 A6683133166
  • Computed with Vd = 2 × K × I × L ÷ CM, K = 12.9 for copper, circular mils from NEC Chapter 9, Table 8. Lengths are rounded down.
  • Breaker sizes are each conductor's 60 °C copper ampacity in NEC Table 310.16. The 80% column is the load a continuous circuit is usually limited to.

NEC references

  • NEC 210.19(A), Informational Note — the 3% branch-circuit voltage drop target
  • NEC Table 310.16 — conductor ampacity behind the breaker sizes
  • NEC 250.122(B) — upsizing the equipment ground when you upsize for drop

Frequently asked questions

How far can you run 12 gauge wire on a 20 amp circuit?

About 45 feet one way at 120 V with the full 20 A on it, keeping drop to 3%. At 16 A (80%) it is 56 feet, and on a 240 V circuit it is 91 feet at 20 A. The NEC sets no maximum length; voltage drop is the limit.

How far can you run 14 gauge wire?

On a 15 A, 120 V circuit, 14 AWG copper reaches about 38 feet one way at full load and 47 feet at 12 A (80%) before passing 3% drop. On 240 V the distances double.

How far can you run 10 gauge wire on 30 amps?

About 48 feet one way at 120 V and 96 feet at 240 V with the full 30 A, keeping drop to 3%. At 24 A (80%) the 240 V run reaches 120 feet.

Why does the chart show an 80% load column?

A circuit feeding a continuous load is sized so that load is no more than 80% of the breaker rating (NEC 210.19(A) and 210.20(A) size continuous loads at 125%). Most real circuits run below the breaker rating, so the 80% column is closer to what a typical run carries.

What do I do if my run is longer than the chart allows?

Upsize the wire. At 120 V and 20 A, 10 AWG copper reaches 72 feet and 8 AWG reaches 115 feet. When you upsize for voltage drop, NEC 250.122(B) requires the equipment grounding conductor to be upsized in proportion.