How Far Can You Run Wire?
Updated 2026-11-22
A 12 gauge copper circuit on a 20 A breaker at 120 V can run about 45 feet one way before voltage drop passes 3%. At 80% load (16 A) that stretches to 56 feet, and on 240 V it doubles to 91 feet. For a longer run, step up to 10 gauge.
The calculator is set for a 120 V, 20 A circuit on 12 AWG copper at 50 feet. Enter your own run length to see whether it stays under 3%.
- 1-phase multiplier 2
- K, copper ×12.9Ch.9 Tbl 8
- Load ×20 A
- One-way length ×50 ft
- #12 AWG circular mils ÷6,530Ch.9 Tbl 8
- Volts lost =3.95 V
- System voltage ÷120 V
- Recommended max Limits≤3%215.2(A)
- Voltage drop =3.29%
Numbers and NEC section numbers only. The AHJ and field conditions govern.
Longest one-way run (feet) at 3% drop, single-phase copper
| Wire · breaker | 120 V · full load | 120 V · 80% load | 240 V · full load | 240 V · 80% load |
|---|---|---|---|---|
| #14 AWG · 15 A | 38 | 47 | 76 | 95 |
| #12 AWG · 20 A | 45 | 56 | 91 | 113 |
| #10 AWG · 30 A | 48 | 60 | 96 | 120 |
| #8 AWG · 40 A | 57 | 71 | 115 | 143 |
| #6 AWG · 55 A | 66 | 83 | 133 | 166 |
- Computed with Vd = 2 × K × I × L ÷ CM, K = 12.9 for copper, circular mils from NEC Chapter 9, Table 8. Lengths are rounded down.
- Breaker sizes are each conductor's 60 °C copper ampacity in NEC Table 310.16. The 80% column is the load a continuous circuit is usually limited to.
NEC references
- NEC 210.19(A), Informational Note — the 3% branch-circuit voltage drop target
- NEC Table 310.16 — conductor ampacity behind the breaker sizes
- NEC 250.122(B) — upsizing the equipment ground when you upsize for drop
Frequently asked questions
How far can you run 12 gauge wire on a 20 amp circuit?
About 45 feet one way at 120 V with the full 20 A on it, keeping drop to 3%. At 16 A (80%) it is 56 feet, and on a 240 V circuit it is 91 feet at 20 A. The NEC sets no maximum length; voltage drop is the limit.
How far can you run 14 gauge wire?
On a 15 A, 120 V circuit, 14 AWG copper reaches about 38 feet one way at full load and 47 feet at 12 A (80%) before passing 3% drop. On 240 V the distances double.
How far can you run 10 gauge wire on 30 amps?
About 48 feet one way at 120 V and 96 feet at 240 V with the full 30 A, keeping drop to 3%. At 24 A (80%) the 240 V run reaches 120 feet.
Why does the chart show an 80% load column?
A circuit feeding a continuous load is sized so that load is no more than 80% of the breaker rating (NEC 210.19(A) and 210.20(A) size continuous loads at 125%). Most real circuits run below the breaker rating, so the 80% column is closer to what a typical run carries.
What do I do if my run is longer than the chart allows?
Upsize the wire. At 120 V and 20 A, 10 AWG copper reaches 72 feet and 8 AWG reaches 115 feet. When you upsize for voltage drop, NEC 250.122(B) requires the equipment grounding conductor to be upsized in proportion.
Related calculators and charts
- Voltage Drop calculator — the full calculator this chart comes from
- 12 V and 24 V DC voltage drop chart
- Three-phase voltage drop at 208 V and 480 V
- How many 12 AWG wires fit in 1/2 EMT?
- How many wires fit in a box?
- Conduit offset bend chart
- All electrician calculators
For guidance only. Always verify against the current National Electrical Code and your local amendments. Fieldwatt does not replace an engineer of record.