Fieldwatt
Field Calc Suite
Offset bends

Conduit Offset Bend Chart

Updated 2026-11-22

For a conduit offset, the distance between bends is the offset depth times the cosecant of the bend angle. At 30° the multiplier is exactly 2.000, so a 6 inch offset needs bends 12.00 inches apart and shrinks the run 1.61 inches. At 45° the multiplier is 1.414; at 22.5° it is 2.613.

The calculator is set for a 6 inch offset at 30°. It uses the rounded multipliers most benders print, so its spacing can differ slightly from the exact values in the chart.

in
Distance Between Bends · 30°
12.00in
Multiplier ×2 · gain/shrink 1.500" — add to your pull length
Mark spacing
12.00"
Multiplier
×2
Shrink
1.500"
90° Stub-up
in
Bend Mark from End · 1/2" EMT
7.0in
Stub 12" − take-up 5". Measure from the conduit end, bend up to 90°.
Hook toward end
Box-offset & 90° stub
Report for your inspector

Offset multiplier, shrink, and distance between bends (inches)

Bend angleMultiplierShrink per inch2 in offset4 in offset6 in offset8 in offset10 in offset
10°5.7590.08711.52 (11 1/2)23.04 (23 1/16)34.55 (34 9/16)46.07 (46 1/16)57.59 (57 9/16)
22.5°2.6130.1995.23 (5 1/4)10.45 (10 7/16)15.68 (15 11/16)20.91 (20 7/8)26.13 (26 1/8)
30°2.0000.2684.00 (4)8.00 (8)12.00 (12)16.00 (16)20.00 (20)
45°1.4140.4142.83 (2 13/16)5.66 (5 11/16)8.49 (8 1/2)11.31 (11 5/16)14.14 (14 1/8)
60°1.1550.5772.31 (2 5/16)4.62 (4 5/8)6.93 (6 15/16)9.24 (9 1/4)11.55 (11 9/16)
  • Multiplier = cosecant of the bend angle. Shrink per inch = cosecant minus cotangent. Distance between bends = offset depth × multiplier, center to center.
  • Distances show decimal inches, then the nearest 1/16 inch for the tape.

NEC references

  • NEC 358.24 — EMT bends must not damage the tubing or reduce its internal diameter
  • NEC 358.26 — no more than 360° of bends between pull points
  • NEC Chapter 9, Table 2 — minimum bending radius by trade size

Frequently asked questions

What is the multiplier for a 30 degree offset?

Exactly 2.000, the cosecant of 30°. Multiply the offset depth by it for the distance between bend marks: a 4 inch offset needs marks 8.00 inches apart. The run shrinks 0.268 inch for every inch of offset, about 1/4 inch.

How do you calculate shrink on an offset?

Shrink per inch of offset is the cosecant minus the cotangent of the bend angle. Multiply it by the offset depth: a 6 inch offset at 45° shrinks 2.49 inches. Add the shrink to your measurement when bending toward an obstruction so the offset lands where you need it.

Why does my bender say 6 for a 10 degree bend?

Printed multipliers are rounded for quick tape math. The exact cosecant of 10° is 5.759, while many benders, and the Fieldwatt calculator above, use 6.0. On a 4 inch offset the rounded value spaces the bends 0.96 inch farther apart.

Which angle should I use for an offset?

Shallow angles like 10° and 22.5° make gentle offsets that pull wire easily but need more straight run. 45° and 60° fit tight spots but add more bend to the raceway. Keep the total between pull points within the 360° limit in NEC 358.26 for EMT.

Take this calculator offline — free on Android

Get it on Google Play

Related calculators and charts

For guidance only. Always verify against the current National Electrical Code and your local amendments. Fieldwatt does not replace an engineer of record.