Conduit Offset Bend Chart
Updated 2026-11-22
For a conduit offset, the distance between bends is the offset depth times the cosecant of the bend angle. At 30° the multiplier is exactly 2.000, so a 6 inch offset needs bends 12.00 inches apart and shrinks the run 1.61 inches. At 45° the multiplier is 1.414; at 22.5° it is 2.613.
The calculator is set for a 6 inch offset at 30°. It uses the rounded multipliers most benders print, so its spacing can differ slightly from the exact values in the chart.
Offset multiplier, shrink, and distance between bends (inches)
| Bend angle | Multiplier | Shrink per inch | 2 in offset | 4 in offset | 6 in offset | 8 in offset | 10 in offset |
|---|---|---|---|---|---|---|---|
| 10° | 5.759 | 0.087 | 11.52 (11 1/2) | 23.04 (23 1/16) | 34.55 (34 9/16) | 46.07 (46 1/16) | 57.59 (57 9/16) |
| 22.5° | 2.613 | 0.199 | 5.23 (5 1/4) | 10.45 (10 7/16) | 15.68 (15 11/16) | 20.91 (20 7/8) | 26.13 (26 1/8) |
| 30° | 2.000 | 0.268 | 4.00 (4) | 8.00 (8) | 12.00 (12) | 16.00 (16) | 20.00 (20) |
| 45° | 1.414 | 0.414 | 2.83 (2 13/16) | 5.66 (5 11/16) | 8.49 (8 1/2) | 11.31 (11 5/16) | 14.14 (14 1/8) |
| 60° | 1.155 | 0.577 | 2.31 (2 5/16) | 4.62 (4 5/8) | 6.93 (6 15/16) | 9.24 (9 1/4) | 11.55 (11 9/16) |
- Multiplier = cosecant of the bend angle. Shrink per inch = cosecant minus cotangent. Distance between bends = offset depth × multiplier, center to center.
- Distances show decimal inches, then the nearest 1/16 inch for the tape.
NEC references
- NEC 358.24 — EMT bends must not damage the tubing or reduce its internal diameter
- NEC 358.26 — no more than 360° of bends between pull points
- NEC Chapter 9, Table 2 — minimum bending radius by trade size
Frequently asked questions
What is the multiplier for a 30 degree offset?
Exactly 2.000, the cosecant of 30°. Multiply the offset depth by it for the distance between bend marks: a 4 inch offset needs marks 8.00 inches apart. The run shrinks 0.268 inch for every inch of offset, about 1/4 inch.
How do you calculate shrink on an offset?
Shrink per inch of offset is the cosecant minus the cotangent of the bend angle. Multiply it by the offset depth: a 6 inch offset at 45° shrinks 2.49 inches. Add the shrink to your measurement when bending toward an obstruction so the offset lands where you need it.
Why does my bender say 6 for a 10 degree bend?
Printed multipliers are rounded for quick tape math. The exact cosecant of 10° is 5.759, while many benders, and the Fieldwatt calculator above, use 6.0. On a 4 inch offset the rounded value spaces the bends 0.96 inch farther apart.
Which angle should I use for an offset?
Shallow angles like 10° and 22.5° make gentle offsets that pull wire easily but need more straight run. 45° and 60° fit tight spots but add more bend to the raceway. Keep the total between pull points within the 360° limit in NEC 358.26 for EMT.
Related calculators and charts
- Conduit Bending calculator — the full calculator this chart comes from
- 12 V and 24 V DC voltage drop chart
- Three-phase voltage drop at 208 V and 480 V
- How far can you run 12 gauge wire?
- How many 12 AWG wires fit in 1/2 EMT?
- How many wires fit in a box?
- All electrician calculators
For guidance only. Always verify against the current National Electrical Code and your local amendments. Fieldwatt does not replace an engineer of record.