Fieldwatt
Field Calc Suite
01 / Circuit

Voltage Drop Calculator

Size a run so the load still gets clean voltage. Keeps you under the 3% branch / 5% total recommendation.

V
A
ft
Voltage Drop
3.29%
7.90 V lost over 100 ft · 232.1 V at the load
Exceeds 3% limit
End voltage
232.1 V
Volts lost
7.90 V
Min size
#10 AWG
↑ Upsize to #10 AWG copper to pass.
NEC 215.2(A) · Ch.9 Tbl 8

How fast is it, really?

Fieldwatt measures input-to-result time on every calculation — the speed claim is a number, not a slogan. Run a few voltage drop calcs above and your typical time appears right here.

Take this calculator offline — free on Android

Get it on Google Play

Voltage drop is the loss of voltage as current flows through a conductor's resistance. The NEC recommends keeping it under 3% on a branch circuit and 5% total for feeder plus branch (210.19(A) and 215.2(A), Informational Notes). For single-phase, Vd = (2 × K × I × L) ÷ CM.

The voltage drop formula

Single-phase:  Vd = (2 × K × I × L) ÷ CM
Three-phase:   Vd = (√3 × K × I × L) ÷ CM
K = 12.9 (copper) or 21.2 (aluminum) Ω·cmil/ft · I = load amps · L = one-way length (ft) · CM = conductor circular mils. Percent drop = Vd ÷ system voltage × 100.

Worked example

A 120 V, 20 A single-phase circuit on #10 copper (10,380 cmil) running 150 ft one-way: Vd = (2 × 12.9 × 20 × 150) ÷ 10,380 = 7.46 V, or 6.2% — over the 3% branch recommendation. Upsizing to #8 copper (16,510 cmil) drops it to 3.9%, and #6 (26,240 cmil) to 2.5%.

Voltage drop on a 120 V, 20 A single-phase copper circuit at common run lengths

One-way length#12 AWG#10 AWG#8 AWG
50 ft3.3%2.1%1.3%
100 ft6.6%4.1%2.6%
150 ft9.9%6.2%3.9%

NEC references

  • NEC 210.19(A), Informational Note — 3% recommended maximum voltage drop on a branch circuit
  • NEC 215.2(A)(1), Informational Note — 5% recommended maximum for feeder + branch circuit combined
  • NEC Chapter 9, Table 8 — conductor properties — circular mils and DC resistance

How to calculate voltage drop

  1. Pick the conductor material (copper or aluminum) and the system voltage.
  2. Enter the load current in amps and the one-way run length in feet.
  3. Choose a wire size — Fieldwatt computes percent drop and end voltage instantly.
  4. If it exceeds 3% on a branch (or 5% total), upsize to the recommended conductor shown.

Frequently asked questions

What is the NEC voltage drop limit?

For most circuits the NEC does not mandate a limit — it recommends a maximum of 3% on a branch circuit and 5% total for feeders plus branch circuits (210.19(A) and 215.2(A) Informational Notes). Some applications (fire pumps, sensitive equipment) and local codes make a limit mandatory.

How do I calculate voltage drop?

Use Vd = (2 × K × I × L) ÷ CM for single-phase (use √3 instead of 2 for three-phase), where K is 12.9 for copper or 21.2 for aluminum, I is load amps, L is the one-way length in feet, and CM is the conductor's circular mils. Divide Vd by the system voltage for percent drop.

Is 3% voltage drop too much?

3% is the NEC's recommended maximum for a branch circuit, so it's the edge of the recommendation, not a failure. Many electricians design to 2% on long or motor circuits to leave headroom. Above 3% on a branch (or 5% total) you should consider upsizing the conductor.

Does voltage drop change the required wire size?

Yes. On long runs, voltage drop — not ampacity — often sets the conductor size. A wire large enough to carry the current can still drop too much voltage over distance, so you upsize until the percent drop falls within the recommendation.

Built for the field

  • Live results as you type — every value recomputes instantly.
  • Works fully offline once the app has loaded.
  • Cites the governing NEC table for every result.
  • Save calculations to a job and build a material list (Pro).

More Fieldwatt calculators

For guidance only. Always verify against the current National Electrical Code and your local amendments. Fieldwatt does not replace an engineer of record.