12V DC Voltage Drop Calculator

Updated 2026-11-22

At 12 volts, a 3% voltage drop is only 0.36 V, so DC runs stay short: 10 AWG copper carrying 10 A reaches about 14 feet one way, and 4 AWG at 30 A about 19 feet. DC uses the two-wire formula. At 24 V the same wire reaches twice as far; at 48 V, four times.

The calculator is set for a 12 V, 10 A run on 10 AWG copper. A DC circuit is a two-wire loop, the same math as a single-phase AC circuit, so leave System on 1-Phase and change the voltage to 24 or 48 for those systems.

V
A
ft
Voltage Drop
2.07%
0.25 V lost over 10 ft · 11.8 V at the load
Within 3% limit
End voltage
11.8 V
Volts lost
0.25 V
Min size
#10 AWG
  1. 1-phase multiplier 2
  2. K, copper ×12.9Ch.9 Tbl 8
  3. Load ×10 A
  4. One-way length ×10 ft
  5. #10 AWG circular mils ÷10,380Ch.9 Tbl 8
  6. Volts lost =0.25 V
  7. System voltage ÷12 V
  8. Recommended max ≤3%215.2(A)
  9. Voltage drop =2.07%

Numbers and NEC section numbers only. The AHJ and field conditions govern.

NEC 215.2(A) · Ch.9 Tbl 8
Report for your inspector

Longest one-way run (feet) at 3% drop on 12 V DC, copper

Wire size5 A10 A20 A30 A50 A
#14 AWG115.72.8 †1.9 †1.1 †
#12 AWG189.14.53.0 †1.8 †
#10 AWG28147.24.82.8 †
#8 AWG4623117.64.6 †
#6 AWG733618127.3
#4 AWG11658291911
#3 AWG14673362414
#2 AWG18592463018
#1 AWG233116583823
1/0 AWG294147734929
2/0 AWG371185926137
  • Computed with Vd = 2 × K × I × L ÷ CM, K = 12.9 for copper, circular mils from NEC Chapter 9, Table 8. Lengths are rounded down.
  • For 24 V multiply each length by 2; for 48 V multiply by 4.
  • † The load is above that size's 60 °C copper ampacity in NEC Table 310.16. Size the wire for current first, then check the run length.

NEC references

  • NEC Chapter 9, Table 8 — circular mil area of each conductor size
  • NEC 210.19(A), Informational Note — the 3% branch-circuit voltage drop target
  • NEC Table 310.16 — copper ampacity used for the † marks

Frequently asked questions

How far can you run 12 volt wire?

It depends on the current and the gauge. Keeping drop to 3% at 12 V, 10 AWG copper carries 10 A about 14 feet one way and 20 A about 7.2 feet. Doubling the current halves the distance, and each size up the table, such as 10 to 8 AWG, adds about 59% more reach.

What voltage drop is acceptable on a 12 V system?

Fieldwatt uses 3%, the branch-circuit target in the NEC 210.19(A) Informational Note. On a 12 V system that is 0.36 V. Pumps, electronics and LED drivers usually need to stay at 3% or less, so check the minimum input voltage on the equipment before you accept more.

Does DC voltage drop use a different formula?

No. A DC run is a two-wire loop like a single-phase AC circuit: Vd = 2 × K × I × L ÷ CM, with K = 12.9 for copper. Enter the one-way length; the 2 accounts for the return conductor. That is why the calculator on this page is set to 1-Phase.

How much farther can I run wire at 24 V or 48 V?

The allowed drop grows with the voltage, so the same wire and current reach twice as far at 24 V and four times as far at 48 V. A 10 A load on 10 AWG copper reaches 14 feet at 12 V, 28 feet at 24 V and 57 feet at 48 V.

Take this calculator offline — free on Android

Get it on Google Play

Related calculators and charts

For guidance only. Always verify against the current National Electrical Code and your local amendments. Fieldwatt does not replace an engineer of record.