12V DC Voltage Drop Calculator
Updated 2026-11-22
At 12 volts, a 3% voltage drop is only 0.36 V, so DC runs stay short: 10 AWG copper carrying 10 A reaches about 14 feet one way, and 4 AWG at 30 A about 19 feet. DC uses the two-wire formula. At 24 V the same wire reaches twice as far; at 48 V, four times.
The calculator is set for a 12 V, 10 A run on 10 AWG copper. A DC circuit is a two-wire loop, the same math as a single-phase AC circuit, so leave System on 1-Phase and change the voltage to 24 or 48 for those systems.
- 1-phase multiplier 2
- K, copper ×12.9Ch.9 Tbl 8
- Load ×10 A
- One-way length ×10 ft
- #10 AWG circular mils ÷10,380Ch.9 Tbl 8
- Volts lost =0.25 V
- System voltage ÷12 V
- Recommended max ≤3%215.2(A)
- Voltage drop =2.07%
Numbers and NEC section numbers only. The AHJ and field conditions govern.
Longest one-way run (feet) at 3% drop on 12 V DC, copper
| Wire size | 5 A | 10 A | 20 A | 30 A | 50 A |
|---|---|---|---|---|---|
| #14 AWG | 11 | 5.7 | 2.8 † | 1.9 † | 1.1 † |
| #12 AWG | 18 | 9.1 | 4.5 | 3.0 † | 1.8 † |
| #10 AWG | 28 | 14 | 7.2 | 4.8 | 2.8 † |
| #8 AWG | 46 | 23 | 11 | 7.6 | 4.6 † |
| #6 AWG | 73 | 36 | 18 | 12 | 7.3 |
| #4 AWG | 116 | 58 | 29 | 19 | 11 |
| #3 AWG | 146 | 73 | 36 | 24 | 14 |
| #2 AWG | 185 | 92 | 46 | 30 | 18 |
| #1 AWG | 233 | 116 | 58 | 38 | 23 |
| 1/0 AWG | 294 | 147 | 73 | 49 | 29 |
| 2/0 AWG | 371 | 185 | 92 | 61 | 37 |
- Computed with Vd = 2 × K × I × L ÷ CM, K = 12.9 for copper, circular mils from NEC Chapter 9, Table 8. Lengths are rounded down.
- For 24 V multiply each length by 2; for 48 V multiply by 4.
- † The load is above that size's 60 °C copper ampacity in NEC Table 310.16. Size the wire for current first, then check the run length.
NEC references
- NEC Chapter 9, Table 8 — circular mil area of each conductor size
- NEC 210.19(A), Informational Note — the 3% branch-circuit voltage drop target
- NEC Table 310.16 — copper ampacity used for the † marks
Frequently asked questions
How far can you run 12 volt wire?
It depends on the current and the gauge. Keeping drop to 3% at 12 V, 10 AWG copper carries 10 A about 14 feet one way and 20 A about 7.2 feet. Doubling the current halves the distance, and each size up the table, such as 10 to 8 AWG, adds about 59% more reach.
What voltage drop is acceptable on a 12 V system?
Fieldwatt uses 3%, the branch-circuit target in the NEC 210.19(A) Informational Note. On a 12 V system that is 0.36 V. Pumps, electronics and LED drivers usually need to stay at 3% or less, so check the minimum input voltage on the equipment before you accept more.
Does DC voltage drop use a different formula?
No. A DC run is a two-wire loop like a single-phase AC circuit: Vd = 2 × K × I × L ÷ CM, with K = 12.9 for copper. Enter the one-way length; the 2 accounts for the return conductor. That is why the calculator on this page is set to 1-Phase.
How much farther can I run wire at 24 V or 48 V?
The allowed drop grows with the voltage, so the same wire and current reach twice as far at 24 V and four times as far at 48 V. A 10 A load on 10 AWG copper reaches 14 feet at 12 V, 28 feet at 24 V and 57 feet at 48 V.
Related calculators and charts
- Voltage Drop calculator — the full calculator this chart comes from
- Three-phase voltage drop at 208 V and 480 V
- How far can you run 12 gauge wire?
- How many 12 AWG wires fit in 1/2 EMT?
- How many wires fit in a box?
- Conduit offset bend chart
- All electrician calculators