Dwelling Load Calculator

Size the service for a one-family house, or check whether the panel you have can take an EV charger or heat pump.

Updated 2026-11-22

New service or a permit worksheet. Every load, its own demand factor.

House

ft²

Required circuits

  • Small-appliance circuit 11,500 VARequired
  • Small-appliance circuit 21,500 VARequired
  • Laundry circuit1,500 VARequired

Appliances

Add each fixed or large appliance. Plug-in kitchen loads ride on the small-appliance circuits.

Enter values to make a report

Enter the house area to start

How fast is it, really?

Fieldwatt measures input-to-result time on every calculation — the speed claim is a number, not a slogan. Run a few dwelling load calcs above and your typical time appears right here.

Take this calculator offline — free on Android

Get it on Google Play

A residential load calculation adds up a home's demand in volt-amperes, applies the NEC demand factors, and divides by 240 V to get amps. If that total is at or under the service rating, the service is big enough. Fieldwatt runs the standard, optional and existing-house methods for NEC 2020, 2023 and 2026.

The dwelling load formula

Standard: lighting = ft² × 3 VA (2026: 2 VA) + 1,500 VA per small-appliance and laundry circuit → first 3,000 VA at 100%, next 117,000 VA at 35%, the rest at 25%.
+ fixed appliances (75% when four or more) + dryer (5,000 W or nameplate, whichever is larger) + range (Column C: 8 kW for one range up to 12 kW, +5% per kW over) + EV charger + the larger of heat or A/C + 25% of the largest motor.
Optional (new house): first 10 kVA of the general load at 100% (2026: 8 kVA), the rest at 40%, plus the heat or A/C selection.
Existing house: first 8 kVA at 100%, the rest at 40% — or the 12-month peak × 125% + the new load.
Amps = total VA ÷ 240 V.

Worked example

A 1,500 ft² house with a 12 kW range and a 5.5 kW dryer (the classic Annex D example), standard method, NEC 2023: lighting 4,500 VA + 3,000 VA small-appliance + 1,500 VA laundry = 9,000 VA, demanded to 3,000 + 6,000 × 35% = 5,100 VA. Add the range at 8,000 VA and the dryer at 5,500 VA for 18,600 VA ÷ 240 V = 77.5 A, inside the 100 A minimum service. At the 2026 rate of 2 VA/ft² the same house comes to 18,075 VA, about 75 A.

Dwelling load values by NEC edition

ItemNEC 2020NEC 2023NEC 2026
General lighting3 VA/ft²3 VA/ft²2 VA/ft²
Lighting sectionTable 220.12220.41120.41
Lighting demand tableTable 220.42Table 220.45Table 120.45
EV charger loadNameplate (no EV section)7,200 VA or nameplate, largerNameplate (7,200 VA if unknown)
Optional method, first tier10 kVA10 kVA8 kVA
Existing house, first tier8 kVA8 kVAUnder review
Energy management625.42 (EV)220.70120.7

NEC references

  • NEC 220.41 (2026: 120.41) — general lighting unit load per square foot — 3 VA in 2020/2023, 2 VA in 2026
  • NEC Table 220.45 (2026: Table 120.45) — lighting demand factors: 100% / 35% / 25%
  • NEC 220.52–220.55 (2026: 120.52–120.55) — small-appliance and laundry circuits, fixed appliances, dryers, and the range table
  • NEC 220.57 (2026: 120.57) — EV charger load (new in 2023)
  • NEC 220.82 (2026: 120.82) — optional method for a new one-family dwelling
  • NEC 220.83 (2026: 120.83) — optional method for an existing dwelling adding load
  • NEC 220.87 (2026: 120.87) — using measured maximum demand for the existing load
  • NEC 220.70 (2026: 120.7) — energy management and power control set-points in the load calc

How to do a residential load calculation

  1. Pick the method: standard for a new service or permit worksheet, optional for a new house on 100 A or more, or existing + add for an EV charger, heat pump or A/C.
  2. Enter the living area in square feet and the service rating. The two small-appliance circuits and the laundry circuit are already counted.
  3. Add each fixed or large appliance with its nameplate rating: range, dryer, water heater, EV charger, heat pump, A/C.
  4. Read the total in amps against the service rating, then open the breakdown to check every line and its NEC section.

Frequently asked questions

How do you do a residential load calculation?

Add the general lighting load (square feet × 3 VA, or 2 VA under the 2026 NEC), 1,500 VA for each small-appliance and laundry circuit, and every fixed appliance, dryer, range, EV charger and the larger of heat or A/C. Apply the demand factors for your method, then divide the total VA by 240 V to get amps.

Do I need a panel upgrade for an EV charger?

Not always. Use the existing-house calc, or take 12 months of utility peak demand × 125% and add the charger. If the total stays at or under the service rating, the panel can carry it. A 48 A charger adds 11,520 VA; when that doesn't fit, a smaller charger or an energy-management set-point often does before you pay for an upgrade. Confirm capacity with your utility.

What is the difference between the standard and optional method?

The standard method applies a separate demand factor to each type of load. The optional method adds the general loads at nameplate, counts the first 10 kVA at 100% (8 kVA in 2026) and the rest at 40%, then adds the heat or A/C selection. For a typical new house the optional method gives a smaller service.

What changed for dwelling load calculations in the 2026 NEC?

The load calculation rules moved from Article 220 to new Article 120. The general lighting load dropped from 3 to 2 VA per square foot, the optional method's first tier at 100% dropped from 10 kVA to 8 kVA, and EV chargers are added at nameplate. Fieldwatt marks its 2026 values as under review until the new existing-dwelling table is verified.

Will a 200 amp service handle a heat pump?

Often, but it depends on the rest of the house. In the existing-house calc, heating or cooling you are adding counts at 100% outside the 40% tier, including the backup heat strip. Compare the total amps with 200 A. Treat it as a planning number; the AHJ and the utility decide.

Field manual

Go deeper on dwelling load

The method, the code article, and the field traps — written out for the cases the calculator only gives you a number for.

  1. Diversity and Demand FactorsWhy the sum of the nameplates is not the service size, and when diversity is allowed.NEC 430.24
  2. Adding EV Charging to an Existing ServiceThe 625 load calculation and the optional method that usually keeps the panel.NEC 625.42
  3. HVAC Loads in a Service CalculationMotor-compressor loads, the 25% adder, and why the largest load is treated differently.NEC Art. 440

Built for the field

  • Live results as you type — every value recomputes instantly.
  • Works fully offline once the app has loaded.
  • Cites the governing NEC table for every result.
  • Export a permit-ready PDF report, save calculations to a job, and build a material list (Pro).

More Fieldwatt calculators

For guidance only. Always verify against the current National Electrical Code and your local amendments. Fieldwatt does not replace an engineer of record. The AHJ and actual field conditions govern.