3-Phase Voltage Drop Calculator

Updated 2026-11-22

Three-phase voltage drop uses √3 instead of 2: Vd = 1.732 × K × I × L ÷ CM. A 30 A load on 10 AWG copper at 208 V drops 3.10% over 100 feet, just over the 3% branch target, while the same run at 480 V drops only 1.35%. Higher voltage carries the same load much farther.

The calculator is set for a 30 A, 208 V three-phase run of 100 feet on 10 AWG copper. Change the voltage to 480, or the length and size, to match your feeder.

V
A
ft
Voltage Drop
3.10%
6.46 V lost over 100 ft · 201.5 V at the load
Exceeds 3% limit
End voltage
201.5 V
Volts lost
6.46 V
Min size
#8 AWG
↑ Upsize to #8 AWG copper to pass. Per NEC 250.122(B), increase the EGC proportionally too.
  1. 3-phase multiplier (√3) 1.732
  2. K, copper ×12.9Ch.9 Tbl 8
  3. Load ×30 A
  4. One-way length ×100 ft
  5. #10 AWG circular mils ÷10,380Ch.9 Tbl 8
  6. Volts lost =6.46 V
  7. System voltage ÷208 V
  8. Recommended max Limits≤3%215.2(A)
  9. Voltage drop =3.10%

Numbers and NEC section numbers only. The AHJ and field conditions govern.

NEC 215.2(A) · Ch.9 Tbl 8
Report for your inspector

Three-phase voltage drop (%) by load, wire size and one-way length, copper

Load · wire208 V · 100 ft208 V · 200 ft208 V · 300 ft480 V · 100 ft480 V · 200 ft480 V · 300 ft
20 A · #12 AWG3.29%6.58%9.87%1.43%2.85%4.28%
30 A · #10 AWG3.10%6.21%9.31%1.35%2.69%4.04%
40 A · #8 AWG2.60%5.21%7.81%1.13%2.26%3.38%
60 A · #6 AWG2.46%4.91%7.37%1.06%2.13%3.19%
100 A · #3 AWG2.04%4.08%6.12%0.88%1.77%2.65%
150 A · 1/0 AWG1.53%3.05%4.58%0.66%1.32%1.98%
200 A · 3/0 AWG1.28%2.56%3.84%0.55%1.11%1.66%
  • Computed with Vd = √3 × K × I × L ÷ CM, K = 12.9 for copper, circular mils from NEC Chapter 9, Table 8, divided by the line-to-line voltage.
  • Wire sizes are a copper size rated for the load at 75 °C in NEC Table 310.16. Anything over 3% fails the branch-circuit target; over 5% fails the feeder-plus-branch target.

NEC references

  • NEC Chapter 9, Table 8 — circular mil area of each conductor size
  • NEC 210.19(A), Informational Note — the 3% branch-circuit target
  • NEC 215.2(A), Informational Note — the 5% feeder-plus-branch target

Frequently asked questions

How do you calculate three-phase voltage drop?

Use Vd = √3 × K × I × L ÷ CM. K is 12.9 for copper or 21.2 for aluminum, I is the line current, L is the one-way length in feet, and CM is the conductor's circular mils from NEC Chapter 9, Table 8. Divide Vd by the line-to-line voltage and multiply by 100 for percent.

Why is three-phase voltage drop lower than single-phase?

In a balanced three-phase circuit the drop is measured line to line, and the drops on two phase conductors sit 120° apart, so they add up to √3 (1.732) times one conductor's drop instead of the 2 of a two-wire circuit. The same current on the same wire loses about 13% fewer volts than it would on a single-phase run.

What size wire do I need for 100 amps at 208 V three-phase over 200 feet?

#1 AWG copper keeps that run to 2.57%, under the 3% target. #3 AWG, which carries 100 A at 75 °C, drops 4.08%. If you upsize for voltage drop, NEC 250.122(B) requires the equipment ground to go up in proportion.

Is 480 V better than 208 V for long runs?

For voltage drop, yes. The same current loses the same volts on the same wire, but that is a much smaller share of 480 V. A 30 A load on 10 AWG copper at 300 feet drops 9.31% at 208 V and 4.04% at 480 V.

Take this calculator offline — free on Android

Get it on Google Play

Related calculators and charts

For guidance only. Always verify against the current National Electrical Code and your local amendments. Fieldwatt does not replace an engineer of record.