3-Phase Voltage Drop Calculator
Updated 2026-11-22
Three-phase voltage drop uses √3 instead of 2: Vd = 1.732 × K × I × L ÷ CM. A 30 A load on 10 AWG copper at 208 V drops 3.10% over 100 feet, just over the 3% branch target, while the same run at 480 V drops only 1.35%. Higher voltage carries the same load much farther.
The calculator is set for a 30 A, 208 V three-phase run of 100 feet on 10 AWG copper. Change the voltage to 480, or the length and size, to match your feeder.
- 3-phase multiplier (√3) 1.732
- K, copper ×12.9Ch.9 Tbl 8
- Load ×30 A
- One-way length ×100 ft
- #10 AWG circular mils ÷10,380Ch.9 Tbl 8
- Volts lost =6.46 V
- System voltage ÷208 V
- Recommended max Limits≤3%215.2(A)
- Voltage drop =3.10%
Numbers and NEC section numbers only. The AHJ and field conditions govern.
Three-phase voltage drop (%) by load, wire size and one-way length, copper
| Load · wire | 208 V · 100 ft | 208 V · 200 ft | 208 V · 300 ft | 480 V · 100 ft | 480 V · 200 ft | 480 V · 300 ft |
|---|---|---|---|---|---|---|
| 20 A · #12 AWG | 3.29% | 6.58% | 9.87% | 1.43% | 2.85% | 4.28% |
| 30 A · #10 AWG | 3.10% | 6.21% | 9.31% | 1.35% | 2.69% | 4.04% |
| 40 A · #8 AWG | 2.60% | 5.21% | 7.81% | 1.13% | 2.26% | 3.38% |
| 60 A · #6 AWG | 2.46% | 4.91% | 7.37% | 1.06% | 2.13% | 3.19% |
| 100 A · #3 AWG | 2.04% | 4.08% | 6.12% | 0.88% | 1.77% | 2.65% |
| 150 A · 1/0 AWG | 1.53% | 3.05% | 4.58% | 0.66% | 1.32% | 1.98% |
| 200 A · 3/0 AWG | 1.28% | 2.56% | 3.84% | 0.55% | 1.11% | 1.66% |
- Computed with Vd = √3 × K × I × L ÷ CM, K = 12.9 for copper, circular mils from NEC Chapter 9, Table 8, divided by the line-to-line voltage.
- Wire sizes are a copper size rated for the load at 75 °C in NEC Table 310.16. Anything over 3% fails the branch-circuit target; over 5% fails the feeder-plus-branch target.
NEC references
- NEC Chapter 9, Table 8 — circular mil area of each conductor size
- NEC 210.19(A), Informational Note — the 3% branch-circuit target
- NEC 215.2(A), Informational Note — the 5% feeder-plus-branch target
Frequently asked questions
How do you calculate three-phase voltage drop?
Use Vd = √3 × K × I × L ÷ CM. K is 12.9 for copper or 21.2 for aluminum, I is the line current, L is the one-way length in feet, and CM is the conductor's circular mils from NEC Chapter 9, Table 8. Divide Vd by the line-to-line voltage and multiply by 100 for percent.
Why is three-phase voltage drop lower than single-phase?
In a balanced three-phase circuit the drop is measured line to line, and the drops on two phase conductors sit 120° apart, so they add up to √3 (1.732) times one conductor's drop instead of the 2 of a two-wire circuit. The same current on the same wire loses about 13% fewer volts than it would on a single-phase run.
What size wire do I need for 100 amps at 208 V three-phase over 200 feet?
#1 AWG copper keeps that run to 2.57%, under the 3% target. #3 AWG, which carries 100 A at 75 °C, drops 4.08%. If you upsize for voltage drop, NEC 250.122(B) requires the equipment ground to go up in proportion.
Is 480 V better than 208 V for long runs?
For voltage drop, yes. The same current loses the same volts on the same wire, but that is a much smaller share of 480 V. A 30 A load on 10 AWG copper at 300 feet drops 9.31% at 208 V and 4.04% at 480 V.
Related calculators and charts
- Voltage Drop calculator — the full calculator this chart comes from
- 12 V and 24 V DC voltage drop chart
- How far can you run 12 gauge wire?
- How many 12 AWG wires fit in 1/2 EMT?
- How many wires fit in a box?
- Conduit offset bend chart
- All electrician calculators
For guidance only. Always verify against the current National Electrical Code and your local amendments. Fieldwatt does not replace an engineer of record.